Usage/Application Office
Alarm Sensor Type Ionization
Brand Ravel
Power Source Electric
Color White
Material Mild Steel
Storage Temperature Range -40 to 85 Degrees Celsius
Operating Temp. -20 to +55 Degrees Celsius
Operating Voltage 14 to 36V DC
Humidity 0 – 93%
Ip Rating IP55
Country of Origin in India
  • Estimated delivery time 14-30 days
  • 18 months warranty at Genuine Warranty Center.
  • Whats in the box: charging cable and block
  Ask a Question
Compare

Product details

Specifications

Operating Voltage : 14 to 36 VDC
Operating current : All operational modes – 5mA; Fast alignment mode – 33mA
Operating temperature : -20 to +55°C
Storage temperature : -40 to +85°C
Relative humidity
(non-condensing or icing)
: 0 to 93%
IP rating : IP55
Housing flammability rating : UL94 V0 polycarbonate

Optical Specifications

Fault level / Rapid obscuration (Δ ≤ 2 seconds) : ≥85%
Maximum angular misalignment of Reflective Detector : ±0.5°
Maximum angular misalignment of Reflector : ±5°
Maximum angular alignment of Reflective Detector : ±4.5°(±70° adjustment bracket accessory)

Detection Performance

Detection range : 0 to 50m
0 to 120m Reflective Long Range Kit
Alignment method : Laser assisted, Auto-AlignmentTM. Manual alignment – optional setting
Auto-AlignmentTM protocol : Background check, Box search, Adjust and Centre
Building Movement TrackingTM : Compensates for natural shifts in alignment from building
movement*
Contamination Compensation : Compensates for gradual build-up of contamination on the optical surfaces
Light Cancellation TechnologyTM : Compensates for high levels of sunlight and artificial lighting
Optical wavelength – smoke detection : 850nm near infrared (invisible)
Integrated laser – laser alignment : 650nm visible. Class IIIa <5mW
Dynamic Beam Phasing : Allows beam detectors to be mounted facing each other the
reflectors in the middle. Eliminates false alarms caused by
Crosstalk between beams
Signal output : Individual Alarm and Fault relays (VFCO) 2A @ 30 VDC

Programmable User Settings

Alarm response threshold levels : 25% (1.25dB – Fastest response to smoke
35% (1.87dB) – Default value
55% (3.46dB) – High immunity to false alarms, slow response to smoke
85% (8.23dB – Highest immunity to false alarms, slowest response to smoke. Configured via the integrated user interface
Delay to Alarm : 10 seconds, for momentary partial obstruction of the beam path
Delay to Fault : 10 seconds, for momentary obstruction of the beam path

Design Parameters

Separation distance between Detector and Reflector : 5 to 50m
50 to 120m Reflective Long Range Kit
Beam path clearance : 1m in diameter from the centre line between Detector and Reflector
Detector dimensions : 130W x 181H x 134D in mm (see diagram)
Reflector dimensions : Up to 50m separation distance – Single reflector 100mm x 100mm x 9mm Up to 120m separation distance – Four reflectors arranged in a square pattern 200mm x 200mm x 9mm
Product weight : Detector – 0.7kg; Reflector – 0.1kg
Multi-detector arrangement : Dynamic Beam Phasing allows for Detectors to face each other the reflectors in the middle
Housing colour : White RAL9016, UV stable